98
MA06-03-1-01
Menu
Parameter
[Direct access]
Description
Default
value
Value
Range
Precondition: Activation via the input for time
control.
t:Turn on delay(ms)
Definition of the delay (in milliseconds) after
which the output is switched on when the input
signal is applied.
2500
0-9999 ms
t:Turn off delay(ms)
Definition of the delay (in milliseconds) after
which the output is switched off when the input
signal is applied.
1500
0-9999 ms
Change to page 074 to configure all inputs/outputs.
[Direct access: CMD -> 7074-> OK]
Parameter
[Direct access]
Description
Default
value
Value Range
Inspection: out of
order
YES enables all "out-of-order" outputs also
in case of inspection.
YES
YES/NO
Recall: out of order
YES enables all "out-of-order" outputs also
in case of recall.
YES
YES/NO
Shutdown: out of
order
YES enables all "out-of-order" outputs also
in case of shutdown.
YES
YES/NO
Fire eme.: out of order
YES enables all "out-of-order" outputs also
in case of fire emergency.
YES
YES/NO
Evacuation: out of
order
YES enables all "out-of-order" outputs also
in case of fire evacuation.