3 — INSTALLATION AND WIRING
pg. 27
Return to TOC Curtis Model 3401T – August 2022
BATTERY CONNECTIONS
Connect the battery to the B+ and B– inputs (pins 16 and 15). Curtis recommends that you
include a fuse in the circuit that connects the battery to the B+ input as shown in Figure 3-2.
The fuse will protect the power system from external shorts and should be sized according to
your applications requirements.
KEYSWITCH
e keyswitch input (pin 7) is active high. Connect the keyswitch input to B+ via a keyswitch.
SWITCH 1–5 INPUTS
e switch 1–5 inputs can be congured for various functions. e following table lists the inputs
pins, functions, and the parameters used to congure the functions:
Switch
Input
Pin Switch
Traction
Fault Code
Hydraulic
Fault Code
Analog Frequency Driver Parameter
1 5 x x x Sender 1 Type
2 13 x x x Sender 2 Type
3 6 x x x Sender 3 Type
4 14 x x x Sender 4 Type
5 8 x x Output Mode
Note: e frequency functions are reserved.
e following sections describe these inputs.
Switch Inputs
e switch 1–4 inputs can be congured as active high (switched to B+) or active low (switched to
B–). If pin 8 is congured as switch input 5, the input is active high. e switches’ statuses can be
used to turn signal icons on or o.
To congure pin 8 as a switch input, set the Output Mode parameter to Switch Input Mode.
e voltage range of the switch inputs is identical to the B+ operating voltage range. e input signals
must be within the range of threshold voltages listed in the following table:
Threshold Minimum Maximum
Active high 4.0V Maximum B+ voltage
Active low N/A 1.0V

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler CURTIS 3401T and is the answer not in the manual?

Kohler CURTIS 3401T Specifications

Power IconPower
nominal voltage12–96 VDC
minimum voltage8 VDC
maximum voltage120 VDC
keyswitch on current33–207mA
keyswitch off current25–112mA
LCD heater on current566–801mA
Operating Environment IconOperating Environment
operating temperature with LCD heater–40°C to +70°C
operating temperature without LCD heater–20°C to +70°C
storage temperature–40°C to +85°C
Weight and Dimensions IconWeight and Dimensions
dimensions160 x 102 x 49.7 mm