Technical data
Updating using Webserver
Updating the inverter using the Webserver is a very
simple process. To do this, simply select the update file
(*.swu) on the computer via the Webserver and start the
installation.
1. Download the update for the inverter from the manu-
facturer's website to your computer.
2. Call up the Webserver Ch. 6.2
3. In the Service menu, go to “Update”.
4. Click on the “Select file” button and select the update
file (*.swu) on the computer or drag the update file
into the field.
5. Start the installation using “Run”.
P
The inverter recognises the update file and starts the
installation.
6. If you want to install the update, confirm the question
with “OK”.
P
The update is installed on the inverter. Once the
update has been installed, the inverter is restarted.
The update may take up to 10 minutes. Following the
update, the successful installation is shown on the
installer’s display.
7. Once the update has been successfully installed,
the current software version can be queried on the
inverter or Webserver.
This is done in the inverter's menu by going to:
Settings/information > Device information or in the
Webserver by going to Info.
H
The update has been installed.
INFO
Following a successful update, the
inverter automatically returns to feed-
in mode.