General area Part 2: Overview of display values and settings
18
Other entries
(General -> Service level)
Select value using Ç => value is displayed
SW NO XXX-XX Software number with index
HS MANUAL Only for HS via eBUS
BURNER TIME 1 H Ä burn time (h) burner 1
BURNER START 1 H Ä Burner starts for burner 1
BURNER TIME 2 H Ä burn time (h) burner 2
BURNER START 2 H Ä Burner starts for burner 2
LIMITER TEST
XX,X°C
Safety temperature limiter test with
heat generator temperature display
Start with Ä (hold down)!
SERVICE
(only with code no.)
Input of date / operating hours for
the yearly maintenance message
RESET USER 00 Load factory settings for user pa-
rameters. (Except language)
RESET EXPERT 00
(only with code no.)
Load factory settings for Expert pa-
rameters.
(Except sensors)
RESET T-PRG 00 Load time program factory settings
RETURN Exit level using Ä
SW NO XXX-XX
Display software number with index (please specify if you
experience problems or have questions about the control-
ler)
HS MANUAL (only with code no.)
Only for HS via eBUS
Open level with
Äand select burner stage using Ç.
After the heat generator Ä
, has been selected, the output
for this heat generator can be set.
With respect to multi-stage heat generators, the second
stage can be activated by presetting an output
value > 50 %.
After closing the service functions the entries are reset au-
tomatically.
BURNER TIME and BURN START (Not for HS via
eBUS)
Ä => Display of current value Ä => Return
Ä hold down until "RESET" display goes off =>
Reset display
LIMITER TEST XX,X°C
Display of heat generator temperature.
Ä Hold down prog. button until LIMITER activates
=> Burner I ON;
all pumps OFF;
all mixers CLOSE
The temperature can be observed in the display.