User Area Part 2: Overview of display values and settings
28
OPT HEAT UP (Heating optimisation)
Activation of function for automatically bringing forward the
start of heating.
Example: Heating program 6.00 hrs – 22.30 hrs
OFF: Building starts to be heated at 6.00 hrs.
ON: Depending on weather and room temperature, heat-
ing starts soon enough so that building just reaches the set
room temperature at 6.00 hrs.
00 => start of heating not brought forward
01 => brought forward depending on weather
02 => brought forward depending on room temperature *)
*) Only active if an FBR analogue room device is connect-
ed (room sensor + operating mode selection).
! Warm-up optimisation occurs only if the reduced
time of the heating circuit is at least 6 hours.
MAX-OPT-TIME (Maximum bring-forward)
Only active with " OPT HEAT UP = 01 or 02"
The start of heating is brought forward by no more than
this time.
OPT REDUCED (Reduction optimisation)
Automatic reduction of burner disabling to end of set heat-
ing time.
The burner is not restarted before the end of the heating
period during the set time period (last heating time only) if
it not already in operation.
This function prevents short-term heating of the heat gen-
erator to the end of the heating period.
PC-ENABLE
Code number for enabling access to heating circuit data
from a PC
"0000" => access is blocked.
RETURN
Exit heating circuit level => Return to "User" area.