Part 2: Overview of display values and settings Expert area
49
T-OUT DELAY (outside temperature delay)
The selected outside temperature delay must be matched
to the type of construction of the building. In the case of
heavy structures (thick walls), a long delay must be select-
ed since a change in outside temperature affects the room
temperature later accordingly. With light structures (walls
have no storage effect) the delay should be set (0 hrs.).
SLOPE OFFSET (heating slope distance)
The heat generator temperature that is required for a mixer
circuit is calculated by adding the calculated temperature
setting for the heating circuit flow to the heating slope dis-
tance. The heating curve distance compensates for sensor
tolerances and heat loss up to the mixer.
B-HEAT SINK (circuit enable)
00 => OFF
01 => The heating circuit can be used by higher-order
functions (e.g. cooling function of a heat generator to pro-
tect from overheating; heat removal during service mode)
as a heat sink/consumer. The heating circuit is heated at
the maximum flow temperature setting for the duration of
the function.