EasyManua.ls Logo

krom schroeder E8 - Effect of the Operating Mode

krom schroeder E8
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Part 1: Operation Operation in normal mode
9
W Service (automatic reset after 15 min)
heat generator regulated to heat generator set temperature
= max. heat generator temperature= see page 35 ; when
the heat generator temperature has reached 65 °C, the
consumers are regulated to their flow temperature to dissi-
pate heat (cooling function).
! The cooling function must be explicitly enabled in
the consumer circuits by means of the parameter
B-HEAT SINK.
Effect of the operating mode
The operating mode set here affects the HS regulation and
the integrated heating circuits of the controller.
Each heating circuit can be assigned a separate operating
mode from the one set by means of the "operating mode"
parameter in the user level of the corresponding heating
circuit.
If the "i = Standby/OFF", and "F = Summer mode" oper-
ating modes are set at the boiler controller, these settings
have a reducing effect on all heating circuits / consumer
circuits that are present in the entire system.
! For mixing controller only on these heating circuits.

Table of Contents