Display Range Part 2: Overview of display values and settings
22
Hot water
T-DHW DES
Current hot water set tempera-
ture according to heating pro-
gram and operating mode
T-DHW Current hot water temperature
T-DHW B
Current temperature of HW tank
in the lower section (charge-
through)
RETURN Exit level using Ä
Heating circuit I / II
T-ROOM DES A
Current room set temperature ac-
cording to heating program and op-
erating mode
T-ROOM Current room temperature
T-POOL DES *) Swimming pool temperature setting
T-POOL *) Current swimming pool temperature
HUMIDITY ***) Current relative humidity
T-DHW DES **) Hot water temperature setting
T-DHW **) Current hot water temperature
T-FLOW DES Current flow temperature setting
T-DHW B **) Lower hot water storage tank temp.
T-DHW F **) Storage tank charging via heat exch.
T-FLOW Current flow temperature
N-OPTI-TIME
Previous time required to heat up
with heat-up optimisation activated
RETURN Exit level using Ä
! Display only appears if the sensor is connected and
the value is present in the system.
If the set value is not present it is masked out, or
hyphens appear in the display (- - - -).
T-DHW B (storage tank lower temperature)
Temperature at lower hot water tank sensor. The value is
only displayed if the value "LOAD THROUGH" is activated
at the level EXPERT => HOT WATER.
T-ROOM DES A (current value for set room tempera-
ture)
If an operator device is connected, there is no display
(“- - - -") in the controller => Value is displayed in the oper-
ator device
T-ROOM (room temperature)
Only if a sensor or an FBR is connected.
*) These values only appear if the heating circuit is pro-
grammed for regulating a pool.
) These values only appear if the heating circuit is pro-
grammed as a hot water circuit.
***) This value is only displayed if an operator device is
connected and the parameters have been set for the cor-
responding heating circuit.
“- - - -„ => no humidity sensor available in operator device