117
9 Appendix
9.13.3 LAMTEC SYSTEM BUS Plug
Use the LSB plug with service-interface to connect a LAMTEC device to the LAMTEC SYS-
TEM BUS. The plug is equipped with circuit board clamps. The clamping points can be held
open with an integrated slide. With this you can position and insert the conductor ends of the
multi conductor bus cable simultaneously. The clamps are suitable for all wire kinds of 0,08
mm
2
.... 0,5 mm
2
The plug has 2 horizontal cable inlets for in- and output, of the LAMTEC SYSTEM BUS. The
plugged cable is connected to the terminals 4, 5 and 6. If You want to connect the LSB to more
LAMTEC devices, use terminals 1, 2 and 3 (terminator OFF). Never use the service and diag-
nose interface.
With a slide-switch you can set the termination of the LSB.
If You place the device at the beginning or the end of the LAMTEC SYSTEM BUS, you must
set the slide of the plug to ON (terminator active).If you place the device at another position of
the LAMTEC SYSTEM BUS, set the slide to OFF (terminator inactive).
Fig. 9-19 pin assignment LSB plug
Technical data
Double cable inlet min. Ø 4,5 mm/ max. Ø 9,5 mm
Baud rate 10kB....1MB
Protection class IP40
Permitted environmental temperature 0
o
C.....+60
o
C
Connection technology „CAGE CLAMP“
terminal strip with activity slide
Tool for clamp screwdriver blade 2,5x0,4 mm
Tool for connector screwdriver blade 3,5x0,5 mm
Tool for strain relief PHO screwdriver