26
5 Commissioning
5.1.19 Burner Firing Rate Controller
5.1.19.1 Enter Set Point Values
Select parameter 796 and 798 (setpoint value 1 and setpoint value 2).
With control by atmospheric condition select additionally parameter 797 and 799.
Nr. FMS ETA Short Text Description Min Max Default
796 0 0 Soll1min Controller setpoint 1 minimum 0 999 90
Firing rate controller setpoint 1 minimum (setpoint 1) in °
C or bar (xx.x)
Set the minimum value for the first controller setpoint
(active if input "set point switching" = 0) (weather guided
controller) in this parameter. If the firing rate controller is
configured as a constant controller, the set point is set
here.
"Set point input via front panel"
1.Selection switch: firing rate value
2.Display: controller setpoint, controller actual value,
firing rate setpoint, internal firing rate
3.Channel key 3 down and channel key 4 up at the
same time
4.Controller setpoint starts to flash and the setpoint can
be changed with channel key 2
5.Do not save value: channel 3 up and channel 4 down
at the same time or switch off burner
6.Save value: save the setpoint to the minimum value
parameter with the Enter key (in P 796 / P 798
depending on the setpoint switching input)
Saving is only possible with constant controller.
With control by atmospheric conditions you may set the
firing rate controller setpoint value default manually
Activation of the controller setpoint modification is disa-
bled when operating mode is OFF. You may not trigger
the burner start by shifting the switching point.
refer to figure "Control by Atmospheric Conditions / Set-
point Switching of the Firing Rate Controller"
Nr. FMS ETA Short Text Description Min Max Default
798 0 0 Soll2min Controller setpoint 2 minimum 0 999 70
Firing rate controller setpoint 2 minimum (set point 2)
in ° C or bar (xx.x)
Enter the minimum value for the second controller set
point (active if input "setpoint switching" = 1) (control by
atmospheric condition). Enter the setpoint in this param-
eter, if the firing rate controller is configured to constant
controller,
see P 796
refer to figure "Control by Atmospheric Conditions
/ Setpoint Switching of the Firing Rate Controller"