24
5 Commissioning
5.1.16 Deactivate Leakage Test
Select parameter no. 772
Select parameter no. 769
Nr. FMS ETA Short Text Description Min Max Default
772 1 2 Dicht.Zü Leak check before ignition (0-OFF / 1-ON) 0 1 1
Setting of the leakage test before ignition:
0 = leakage test is off before ignition
1 = leakage test is on before ignition
This parameter is only of significance if the leakage test
is activated with an FMS. (Parameter 3)
Nr. FMS ETA Short Text Description Min Max Default
769 1 2 D.n.Abs Leak check after switching off (0-OFF / 1-ON) 0 1 0
Select the leakage test after switch off (only FMS and
ETAMATIC with integral leakage test)
0 = leakage test off after switch OFF
1 = leakage test on after switch OFF
Activate the function of this parameter with the release
of the leakage test (P 3).
If the leakage test is not available after switching off
(with fault shutdown or voltage loss), a leakage test is
automatically performed before restart even if P 772 is
set to 0.