136
9 Appendix
The new EPROMs will change CRC 4.
Correct the software version on the configuration label.
Send both, the CRC4 check sums and the new software version to LAMTEC. LAMTEC
needs this data to complete the device’s CV
NOTICE
Note that LAMTEC redesigns the internal burner firing rate controller in software version
A4a300. It depends on the software version you are using before the update if you must
change parameter 805 and parameter 808.
Some empirical values:
Individual optimisation provided by customer.
9.23 Wiring Notes
9.23.1 Shields Connection
All cables from and to the ETAMATIC must be shielded (with the exception of the 230 V cable).
Connect the shielding to PE by the shortest possible route.
9.23.2 PE Busbar
Two rails are fitted to the left and right side of the terminal strips and parallel to them on the
unit's rear side. Connect all shieldings to these rails. Also connect the PE to this point from
the outside.
847 1
935 10
Parameter Description Hot Water Steam
805 P term 120 280 600
806 I term 60 360 300
807 D term 20 50 35
808 Adjustment time 15 2 20
Right:
shielding terminal
connection terminal
Wrong:
connection terminal
shielding terminal