5 Commissioning
5.1.7 Start with or without Pilot Burner
Select parameter no. 774 and 775 (oil operation, gas operation).
NOTICE
2 to 4, 9, 11, 17, 19, 25, 27 The ignition flame input must monitor the ignition flame sep-
arately and P 788 must be set to 1.
9, 11 FMS only
17, 19, 25, 27 FMS with mixed fuel firing only
Nr. FMS ETA Short Text Description Min Max Default
774 1 1 ZüBr. ÖL Start with (1) or without (0) pilot burner for oil, (2)=oil
with continuous ignition flame
0 255 1
0 = start without pilot burner - oil operation
1 = start with pilot burner - oil operation
2 = pilot burner also active in burner operation with
continuous monitoring of the ignition flame.
Therefore P 788 has to be set to 1
3 = start with pilot burner - oil operation,
only the ignition flame may be present during ignition
(until the 2
nd
safety time)
4 = pilot burner also active in operation with continuous
operation monitoring of the ignition flame, only the
ignition flame may be present during ignition
(until the 2
nd
safety time)
(from v. 5.4/510 on)
9 = start with pilot burner - oil operation
You may start the pilot burner with terminal 70 dur-
ing operation.
11 = start with pilot burner - oil operation
only the ignition flame may be present during igni-
tion (until the 2
nd
safety time).
You may start the pilot burner with terminal 70 dur-
ing operation.
17 = start with pilot burner - oil operation
Before curve set change from solo operation (gas/
fuelA) to mixed mode (+oil), the pilot burner starts
to ignite oil.
19 = start with pilot burner - oil operation,
only the ignition flame may be present during igni-
tion (until the 2
nd
safety time).
Before curve set change from solo operation (gas/
fuelA) to mixed mode (+oil), the pilot burner starts
to ignite oil.
25 = start with pilot burner - oil operation,
You may start the pilot burner with terminal 70 dur-
ing operation.
Before curve set change from solo operation (gas/
fuelA) to mixed mode (+oil), the pilot burner starts
to ignite oil.
27 = start with pilot burner - oil operation,
only the ignition flame may be present during igni-
tion (until the 2
nd
safety time).
You may start the pilot burner with terminal 70 dur-
ing operation. Before curve set change from solo
operation (gas/fuelA) to mixed mode (+oil), the pilot
burner starts to ignite oil