5 Commissioning
Select active channel
Select parameter 366 and 367 (curve set 1 and 2).
Controller release with bit pattern.
Nr. FMS ETA Short Text Description Min Max Default
366 2 2 K Enb. 1 Channel enable for curve set 1 0 31 15/31
This parameter defines, which channel is active with
which curve set. All channels are active by default (con-
tent 31, in ETAMATIC 15). The following function may
be realised. Example:
changing channel activities with fuel oil/gas
emergency operation with or without frequency con-
verter
Selection per binary pattern:
with 15, all 4 channels are released for operation
with 31, all 5 channels are released for operation
Example ETAMATIC:
Channel 1, 2 and 5 are released
Default settings at delivery:
curve set 1 (oil) = 1011
curve set 2 (gas) = 1101