31
5 Commissioning
5.2.2.2 Clear Memory
5.2.3 Programming the Ignition Point
5.2.4 Programming the Base Firing Rate
5.2.5 Programming the 3rd up the 10th Point
Proceed as described in "Program base firing rate point", but set each of the firing rate ratings
“250", "300", "400", "500", "600", "700", "800", "900", and "999" one after the other.
Press key 16 twice ("setpoint" display)
Press key 14 twice the display shows SL in its centre.
Press Enter key 11 “ENTER” the display shows "cleared", the old curve is
cleared.
Press key 13 the display shows "El" in its centre.
Start burner (signal at terminal 58) and wait until pre-purge has ended.
Use keys 16 and 17 to switch to "setpoint"
Use keys 2 to 9 to run the control elements to ignition position
Press key „ENTER“ the display shows "Really ignite"
If not, press key 3 and redefine ignition position.
Press key “ENTER” again to confirm. Burner ignites.
Use keys 16 and 17 to switch to "firing rate value"
Use keys 2 and 3 to set "200"
Use keys 16 and 17 to switch to "actual value feedback"
Use keys 2 to 9 to run control elements to base firing rate position.
Press key ENTER.