5 Commissioning
5.1.15 Parameters of the Interface
NOTICE
These parameters have to be equal to the settings of the remote control software.
Otherwise no communication is possible.
Nr. FMS ETA Short Text Description Min Max Default
822 2 2 Baud S1 Baud rate of serial interface 1 0 5 4
This parameter sets the baud rate for the serial inter-
face. The standard value is parameter content "4"
(19,200 baud). If the display shows problems with the
serial transmission (especially with long serial connec-
tions), it may be helpful to drop the baud rate. This must
be carried out on the VMS/FMS/ETAMATIC as well as
on the operating device e.g. laptop.
0 = 1200 Baud 3 = 9600 Baud
1 = 2400 Baud 4 = 19 K 2 Baud
2 = 4800 Baud 5 = 38 K 4 Baud
824 2 2 Par. S1 Parity check for serial transfer (ser.1)1 0 2 1
This parameter sets the parity bit for interface transmis-
sion. Standard is even (parameter content: EVEN=0,
NONE=1, ODD=2).
0 = even
1 = none
2 = odd
826 2 2 Adr. S1 Network address VMS/FMS (ser.1)1 0 31 1
Network address VMS / FMS (serial Interface 1)
Enter the network address for the serial interface. Fac-
tory status for the network address is 1. Only if several
devices are connected via an RS422/RS485 bus, this
network address has to be changed.