EasyManua.ls Logo

Lamtec ETAMATIC - Manual Calculating and Setting of the Control Parameters; Guidelines

Lamtec ETAMATIC
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
48
6 O
2
Trim
6.9.6.2 Manual Calculating and Setting of the Control Parameters
Set firing rate controller to "Manual” and run to low firing-rate.
Enter password (see chapter ExternalLink: Passworteingabe)
Key 7 more O
2
Key 6 less O
2
You should choose the setting of parameters 898 and 899 in that way, that the next setpoint
value/actual value comparison (control pulse) only takes place if the actual O
2
value has
changed visibly (~ 60% of end value). A mark at the centre of the setpoint display indicates
that a setpoint / actual value comparison has just been performed.
No change, or change too small Increase P term, parameter 899.
6.9.6.3 Guidelines
Enter the calculated value in parameter 898.
Factory setting: 15 seconds.
The dead time is weighted as a function of firing rate.
The dead time reduces at high fire due to the higher gas velocities. The factory setting is A
reduction of 3 seconds in dead time.
Procedure for calculating the dead time at high fire, as described above.
Set the P-term in that way, that a deviation of 1…2 vol.% O
2
between target and actual value
is corrected within 4…6 steps without overshooting.
Repeat until the setpoint is reached within ca. 4…6 steps. Check control unit setting at medi-
um and high fire.
NOTICE
You may use the P-term (parameter 899) and the dead time (parameters 898 and 900) to
achieve optimisation which inter alia depends on the installation's properties; e.g. a shorter
dead time can be set if the P-term is reduced at the same time.
Recommendation:
Set control unit speed a bit slower and P-term smaller safer!!!
Set base value for "Deactivated control” and "Air deficiency”
press keys 13 and 14 to select "Set O
2
"
press key 8 to confirm the query
press key 16 until the display shows "setpoint"
press key 5 up, to activate the O
2
trim during adjustment. the display shows "T"
use the keys 6 and 7 to change the O
2
setpoint from the preset value with the range
+3 to -1 vol.% O
2
. Observe the change in the actual O
2
value simultaneously on the
display.
Control pulses too short increase P-term, parameter 899
Overshooting reduce P-term

Table of Contents

Other manuals for Lamtec ETAMATIC

Related product manuals