EasyManua.ls Logo

Lamtec ETAMATIC - Page 127

Lamtec ETAMATIC
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
126
9 Appendix
If the set pulse range is exceeded the value remains at the upper end of the range (higher
pulse numbers are ignored). Below the measuring range the signal goes to approx. 0 - 7 digit.
WARNING!
Make sure that the selected measuring range is not exceeded, otherwise speed changes in
excess of this will no longer be detected.
Fig. 9-28 R.p.m.board 663P8012 type plate
Fig. 9-29 R.p.m. board 663P8012
Fig. 9-30 Basic board ETAMATIC S
Fig. 9-31 R.p.m. board built in on basic board
No. Description
1 Plug-in position r.p.m. board on basic board ETAMATIC S
2 R.p.m. board 663P8012 built in basic board
Technical Data
Linearity error: < 0,1 % v. E.
Temperature drift: < 75 ppm/K (typical 60 ppm/K)
NAMUR-input: U
0
= 8,2 V; Ik = 8,2 mA, +/-5 %
Make threshold: max. 2,1 mA (typical 1,8 mA), +/-5 %
Break threshold: max. 1,2 mA (typical 1,4 mA), +/-5%
Switch input:
Make threshold: 6,2 V

Table of Contents

Other manuals for Lamtec ETAMATIC

Related product manuals