EasyManua.ls Logo

Lamtec ETAMATIC - 7 Internal Burner Firing Rate Controller

Lamtec ETAMATIC
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51
6 O
2
Trim
Nr. FMS ETA Short Text Description Min Max Default
902 1 1 O2NeutrB Correction value output when O
2
trim is deactivated. 0 1000 400
Correction value is displayed at deactivated O
2
trim.
Fuel 1
(from 5.0 on):
at P 7 = dec 32 and P 847 = 2, 3 or 4:
CO/O
2
controller slave / correction 1 via LSB
0 = the last received value is permanent valid
1..65535 = Time-out in seconds after P 901 / P 902 is
active.
917 1 1 LftmKorA Air deficiency correction value fuel A 0 999 300
Air deficiency correction value for fuel 1
918 1 1 LftmKorB Air deficiency correction for fuel B
see P 917
0 999 300

Table of Contents

Other manuals for Lamtec ETAMATIC

Related product manuals