8 Control Mode
As soon as one of the following incidences happen, the parameter set ignition sequence of
the fuel is executed without switching on the ignition transformer:
Boiler pressure or boiler temperature have lapsed to that point, where the burner would
start again (with internal firing rate controller)
As soon as the LSB contact (terminal 1) opens again.
As soon as the command is transferred by fieldbus.
This may occur after valve leakage test, before operation, with fuel gas and without the trans-
former leading time (analogue changing by pilot burner ignite the new fuel)
NOTICE
At combustion plants with just one flame detector, ensure, that the main flame is always ignit-
ed by the pilot flame. Otherwise use one flame detector for the main flame and one for the pilot
flame.
If the "Burner ON" signal will be removed during stand-by mode, the Gerät switches OFF. This
shut-off proceeds like a shut-off out of the modes BASE FIRING RATE/CONTROL with all it’s
parameter set procedures.
In oil operation the output for the oil pump stays active.
LSB module address 31 input 1
NOTICE
Since it's not sure how long the STANDBY mode applies, a separate pilot flame monitoring
must be approved for continuous operation, or main flame and pilot flame are monitored to-
gether with one flame scanner, approved for continuous operation.