Selection of the contr ol mode
8
Commissioning
8.3
L
8.3-2
EDS82EV903-1.0-11/2002
The following table helps you to find the correct operating mode for standard
applications:
Application Operating mode
Setting in C0014
Single drives recommended alternatively
with extremely alternating loads 4 2
with heavy start conditions 4 2
with speed control (speed feedback) 2 4
with high dynamic response (e. g. positioning and infeed drives) 2 -
with torque setpoint 5 -
with torque limitation (power control) 2 4
Three-phase AC reluctance motors 2 -
Three-phase sliding rotor motors 2 -
Three phase motors with assigned frequency-voltage characteristic 2 -
Pump and fan drives with square-law load characteristic 3 2or4
Group drives
(several motors connected to controller)
identical motors and identical loads 2 -
different motors and/or changing loads 2 -
C0014 = 2: linear V/f characteristic control
C0014 = 3: square -l aw V/F characteristic control
C0014 = 4: vector control
C0014 = 5: senso rless torque control
Operating modes recommended
for standard applications