Parameter setting with the E82ZBC keypad
V/f char acteristic control
8
Commissioning
8.4
8.4.1
L
8.4-2
EDS82EV903-1.0-11/2002
Switch-on sequence Note
1. Attach the keypad
2. Ensure that controller inhibit is active after mains connection.
misc001
20 28
X3
}
Terminal X3/28 = LOW
3. Switch on the mains
ON
misc002
4. The keypad is in “Disp” mode after approx. 2 s and indicates the
output frequency (C0050)
PS
mno
p
qr
Hi
Hz
Lo
The menu USEr is active
5. Change to the f mode to configure the basic settings for your
drive
Hi
Hz
Lo
PS
Blinking on the display: 0050
6. Adapt the voltage range/current range to the analog setpoint
(C0034)
Lenze setting: - 0-, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
PS
mno
p
qr
Hi
Hz
Lo
Set the DIP switch on the standard I/O to the same
range (see Mounting Instructions for the
standard I/O)
7. Adapt the t e rminal configuration to the wiring (C0007)
Lenze setting: -0-, i. e.
E1: JOG1/3 f ixed setpoint selection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW operation
PS
mno
p
qr
Hi
Hz
Lo
8. Set the minimum output fre quency (C0010)
Lenze setting: 0.00 Hz
[f]
C0011
9. Set the ma ximum output fre quency (C0011)
Lenze setting: 50.00 Hz
0%
100 %
C0010
10. Set the acceleration time T
ir
(C0012)
[ H z ]
2
C 0 0 1 1
1
0
t
i r
t
i f
T
i r
T
i f
t
T
ir
= t
ir
⋅
C0011
f
2
− f
1
.
[ H z ]
2
C 0 0 1 1
1
0
t
i r
t
i f
T
i r
T
i f
t
t
ir
= acceleration time wanted
11. Set the deceleration time T
if
(C0013)
[ H z ]
2
C 0 0 1 1
1
0
t
i r
t
i f
T
i r
T
i f
t
T
if
= t
if
⋅
C0011
f
2
− f
1
.
[ H z ]
2
C 0 0 1 1
1
0
t
i r
t
i f
T
i r
T
i f
t
t
if
= deceleration time wanted
12. Set the V/f-rated frequency (C0015)
Lenze setting: 50.00 Hz
100%
V
out
13. Set the V
min
boost (C0016)
Lenze settings: Depending on the controller type
0
0 C0015
V
min
f
The Lenze setting is suitable for all common
applications
14. If you want to change the settings, please go to the menu ALL . activate e. g. JOG frequencies
(C0037, C0038, C0039) or
motor temperature monitoring
(C0119)
When you are ready with parameter setting:
15. Setpoint selection e. g. via potentiometer at the
terminals7,8,9
16. Enable the controller.
20
28
X3
misc002
Terminal X3/28 = HIGH
17. The drive should be running now at e.g. 30 Hz
PS
mno
p
qr
Hi
Hz
Lo
If the drive does not start, press u in addition.