Thermal motor monitoring
Temperature monitoring of the motor with PTC and earth-fault detection
10
Function library
10.14
10.14.2
L
10.14-4
EDS82EV903-1.0-11/2002
Codes for parameter setting
Code Possible settings IMPORTANT
No. Name Lenze Selection
C0119 Configuration of 0
0 PTC input not active
Earth fault detection • Signal output configuration under C0415 ^
v
48
motor temperature
monitoring (PTC
1 PTC input active,
TRIP set
active
• If several parameter sets are used, the
monitoring must be separately adjusted
10.14-3
nput
eart
au
t
detection
2 PTC input active,
Warning set
for each parameter set.
• Deactivate the earth fault detection, if it
3 PTC input not active
Earth fault detection
.
• If the earth fault detection is active
the
4 PTC input active,
TRIP set
,
motor starts after controller enable with
a delay of approx.40 ms.
5 PTC input active,
Warning set
)
))
) Note!
l In the Lenze setting, the temperature monitoring of the motor is
switched off!
l If you are dealing with several parameter sets, you must
activate the monitoring in each parameter set!
1. Connect the monitoring circuit of the motor to X2/T1 and X2/T2.
– If 1.6 kΩ <R<4kΩ the monitoring is activated.
2. Set the reaction of the controller:
– C0119 = 0 or 3: Temperature monitoring of the motor is switched off
– C0119 = 1 or 4: TRIP fault message (keypad display: OH3 a)
– C0119 = 2 or 5: Warning signal (keypad display: OH51 e)
Connect the PTC input to a fixed resistor:
l R>4kΩ: A fault message OH3 or OH51 must be initiated.
l R<1kΩ: A fault message must not be initiated.
Activation
Verification