Operation with rated power (normal operation)
Rated data for mains voltage 500 V
4
Technical data
4.3
4.3.3
L
4.3-12
EDS82EV903-1.0-11/2002
Typical motor p ower
P
r
[kW] 18.5 30 37
Three-phase
C asynchronous motor
(4 pole)
P
r
[hp] 25 40 49.5
8200 vector type With mains filter E82EV153K4B3xx E82EV223K4B3xx E82EV303K4B3xx
Without mains filter E82EV153K4B2xx E82EV223K4B2xx
1)
E82EV303K4B2xx
1)
Mains voltage U
mains
[V] 3/PE AC 320 V - 0 % ... 550 V + 0 % ; 45 Hz - 0 % ... 65 Hz + 0 %
Alternative DC supply U
DC
[V] DC 450 V - 0 % ... 775 V + 0 %
Data for op eration with 3/PE AC 500 V or DC 710 V
Rated mains current
without mains choke/mains f ilter I
mains
[A] 43.5 - -
with mains choke/mains filter I
mains
[A] 29.0 42.0 55.0
Output power U, V, W S
r
[kVA] 26.6 39.1 49.9
Output power +U
G
,-U
G
2)
P
DC
[kW] 11.8 4.6 0
Rated output current at 1kHzsin
chopper frequency
2kHzsin I
r
[A]
5)
30.5 45 56
4kHzsin
8kHzsin I
r
[A] 27 41 44
5)
16 kHz sin
4)
I
r
[A] 19 28 30
1kHz
2kHz I
r
[A] 32 47 56
4kHz
8kHz I
r
[A] 32 47 56
16 kHz
4)
I
r
[A] 22 33 41
Max. permissible 1kHzsin
output current for 60 s
2kHzsin I
max
[A] 46 66.5 65
at chopper frequency
3)
4kHzsin
8kHzsin I
max
[A] 41 61 65
5)
16 kHz sin
4)
I
max
[A] 29 42 45
1kHz
2kHz I
max
[A] 48 70.5 84
4kHz
8kHz I
max
[A] 48 70.5 84
16 kHz
4)
I
max
[A] 33 49 61
Output voltage
without mains choke/mains f ilter U
M
[V] 3~ 0 ... V
mains
/ 0 ... 650 H z
with mains choke/mains filter U
M
[V] 3~ 0 ... approx. 94 % U
mains
/ 0 ... 650 H z
Power loss (operation with I
r8
) P
v
[W] 430 640 810
Required mains choke Type - ELN3-0075H045 ELN3-0055H055
Dimensions
with mains f ilter H x W x D [mm] 350 x 250 x 340
without mains filter H x W x D [ mm] 350 x 250 x 250
Weight
with mains f ilter m[kg] 34
without mains filter m[kg] 15
Printed in bold = Data for operation at 8 kHz chopper frequency (Lenze setting)
1)
Operation only with mains choke or mains f ilter
2)
For operation with power-adapted motors additional power to be t aken from the DC bus
3)
Currents for periodic load change : 1 min overcurrent with I
max
and 2 min basic load with 75 % I
r
4)
Chopper frequency is reduced to 4 kHz if Ï‘
max
reaches - 5 °C
5)
Operation o nly with automatic chopper frequency reduction (C0144 = 1). Ensure not to e xceed the declared
current s.