7 Fieldbus
Profibus quick start
Lenze · Inverter i510 / i550 - Cabinet · Operation Manual · 0.4 EN · 02/2016 101
7.3 Profibus quick start
1. Set an individual node address:
i550: Dip-Switches or Parameter setting P510:1 (0x2341.1)
The active node address will be displayed in P511:1 (0x2342.1)
2. Save the parameters (P700:3, 0x2022:3) and power cycle the drive completely that the configuration takes
effect.
3. Configuration of the host:
Read the device description file (GSD) into the Profibus master.
i
4. Process data configuration
The process data configuration must be configured in the Profibus master configuration tool.
The default configuration in the i550 GSD-file is:
PLC to Drive:
Lenze control word (NetWordIN1) P590:1 (0x4008:1)
Network frequency setpoint 0.01Hz P592:5 (0x400B:5)
16Bit selectable OUT-Data
Drive to PLC:
Lenze status word (NetWordOUT1) P591:1 (0x400A:1)
Actual Speed [0.01 Hz] P593:6 (0x400C:6)
Actual motor current [0.1A] P104 (0x2D88)
i