6 Function & parameter description
Control concept
Lenze · Inverter i510 / i550 - Cabinet · Operation Manual · 0.4 EN · 02/2016 41
Run Forward/Reverse (Steady Signals)
Start using steady signals Run Forward (CW) and Run Reverse (CCW). If no Run command is active the motor
will stop according the selected stop method (P203:3)
Inverter enable Level Low will stop the inverter with a coast stop.
GND
AO1
AI2
AI1
DI1
24V
10V
DI5
DI4
DI3
DI2
GND
DO1
Run Forward (CW)
Control Wiring
Run Reverse (CCW)
P400:8
P400:9
NO
COM
NC
1k … 10k
Potentiometer
DI2
DI3
Expected Behavior
50 Hz
AI1
Mains
50 Hz
0 Hz
-50 Hz
P220:0 Acceleration
time 1
Stop method
based on
P203:3
Motor
Speed
DI1
Inverter enable
P400:1
Stop method based
on P203:3