3-phase mains connecon 400 V "Light Duty"
Connecon diagrams
4Connecon diagrams ^ 145
Terminal data
4Terminal data ^ 146
Fusing data
A residual current device (RCD) is oponal.
Fusing data for UL/NEC compliant installaons: 4Fusing data ^ 135
Inverter Fuse Circuit breaker RCD
Characterisc
Max. rated
current
Characterisc
Max. rated
current
Type
A A mA
I55AP137F..3 gG/gL, gRL 40 B 32 ≥30 Typ B
I55AP155F..3 gG/gL, gRL 40 B 32 ≥30 Typ B
I55AP175F..3 gG/gL, gRL 40 B 32 ≥30 Typ B
I55AP211F..3 gG/gL, gRL 40 B 32 ≥30 Typ B
I55AP215F..3 gG/gL, gRL 40 B 32 ≥30 Typ B
I55AP222F..3 gG/gL, gRL 40 B 32 ≥30 Typ B
I55AP230F..3 gG/gL, gRL 50 B 50 ≥30 Typ B
I55AP240F..3 gG/gL, gRL 50 B 50 ≥30 Typ B
I55AP255F..3 gG/gL, gRL 50 B 50 ≥30 Typ B
I55AP275F..3 gG/gL, gRL 50 B 50 ≥30 Typ B
I55AP311F..3 gG/gL, gRL 50 B 50 ≥30 Typ B
Electrical installaon
Mains connecon
3-phase mains connecon 400 V "Light Duty"
148