3-phase mains connecon 480 V "Light Duty"
Rated data
The output currents apply to these operang condions:
•
At switching frequency 2 kHz or 4 kHz: Ambient temperature max. 40 °C (104 °F).
Inverter I55AP
137F 155F 175F 211F 215F 222F 230F 240F 255F 275F 311F
Rated power P
rated
kW 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15
Rated power P
rated
HP 0.75 1 1.5 2 3 4 5 7.5 10 15 20
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0 - 400/480 V
Rated mains current
without mains choke A 1.5 2.1 3.9 4.2 5.1 7.3 8.6 11.2 15.3 22 30.5
with mains choke A -
Apparent output power kVA 1.3 1.7 2.4 2.8 3.9 5.1 6.6 8.9 11.3 16.9 21.7
Rated output current
2 kHz A 1.3 1.9 2.5 3.6 4.2 5.8 7.6 9.8 13.2 18.3 25.2
4 kHz A 1.3 1.9 2.5 3.6 4.2 5.8 7.6 9.8 13.2 18.3 25.2
Power loss
2 kHz W 24 30 38 45 62 79 102 137 172 242 340
4 kHz W 25 32 40 48 66 84 108 145 183 258 361
Cyclic mains switching 3 mes per minute
Max. motor cable length
shielded
without EMC category m 50
Category C1 (2 kHz, 4 kHz,
8kHz)
m 3 -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 20
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 35
Max. motor cable length
unshielded
without EMC category m 60 80 100 200
Degree of protecon
EN IP31
NEMA Type 1
Weight m kg 1.7 2.6 4.8 5
Weight m lb 3.7 5.7 10.6 11
Technical data
3-phase mains connecon 480 V "Light Duty"
Rated data
191