EMC-compliant installaon
The drive system (inverter and drive) only complies with the EMC Direcve 2014/30/EU if it is installed
according to the guidelines for CE-typical drive systems.
These guidelines should also be followed in installaons requiring FCC Part 15 or ICES 001 compliance.
NOTICE
Electromagnec interferences
Product and peripheral devices may be aected during operaon.
▶
Use integrated conducve shield connecons for control lines and motor lines.
▶
Use central earthing points.
The following example shows the eecve wiring:
A Shield connecon for control connecons
B Control line
C EMC cable gland
D Motor cable with low capacity
E Power line
EMC-compliant installaon must be implemented with shielded motor cables of low capacitance.
Capacitance per unit length:
•
C-core-core/C-core-shielding: < 75/150 pF/m ≤ 2.5 mm² (≥ AWG 14);
•
C-core-core/C-core-shielding: < 150/300 pF/m ≥ 4 mm² (≤ AWG 12)
Electrical installaon
EMC-compliant installaon
133