3-phase mains connecon 230/240 V "Light Duty"
Rated data
The output currents apply to these operang condions:
•
At switching frequency 2 kHz or 4 kHz: Ambient temperature max. 40 °C (104 °F).
Inverter I55AP
137D 155D 175D 211D 215D 222D 230C 240C 255C 275C
Rated power P
rated
kW 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11
Rated power P
rated
HP 0.75 1 1.5 2 3 4 5 7.5 10 15
Mains voltage range 3/PE AC 195 V ... 264 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0 - 230/240 V
Rated mains current
without mains choke A 4.7 5.8 7.7 9.4 11.4 16.4 17.3 23.8 33.1 40
with mains choke A -
Apparent output power kVA 1.2 1.6 2.2 2.6 3.6 4.9 6.2 8.7 11 15.8
Rated output current
2 kHz A 2.9 3.8 5 7.2 8.4 11.5 14.4 19.8 27.6 34.8
4 kHz A 2.9 3.8 5 7.2 8.4 11.5 14.4 19.8 27.6 34.8
Power loss
2 kHz W 30 38 45 62 79 102 137 172 242
4 kHz W 32 40 48 66 84 108 145 183 258
Cyclic mains switching 3 mes per minute
Max. motor cable length
shielded
without EMC category m 50
Category C1 (2 kHz, 4 kHz,
8kHz)
m -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m -
Category C3 (2 kHz, 4 kHz, 8
kHz)
m -
Max. motor cable length
unshielded
without EMC category m 60 80 100 200
Degree of protecon
EN IP31
NEMA Type 1
Weight m kg 1.6 2.5 4.7 4.9
Weight m lb 3.5 5.5 10.4 10.8
Technical data
3-phase mains connecon 230/240 V "Light Duty"
Rated data
184