Technical data
Standards and operang condions
Conformies and approvals
Conformies
CE
2014/30/EU EMC Direcve (reference: CE-typical drive system)
2014/35/EU Low-Voltage Direcve
EAC
TP TC 020/2011
Eurasian conformity: Electromagnec compability of
technical means
TP TR 004/2011 Eurasian conformity: Safety of low voltage equipment
RoHS 2011/65/EU
Restricons on the use of certain hazardous substances
in electrical and electronic devices
Approvals
UL UL 61800-5-1
File No. E132659
for USA and Canada (requirements of the CSA 22.2 No.
274)
Protecon of persons and device protecon
Degree of protecon Informaon applies to the mounted and ready-for-use
state
EN EN 60529
IP31
IP66
NEMA NEMA 250
Type 1
Type 4X outdoor
UL
UL 50 Type 1
UL 50E Type 4X outdoor
Insulaon resistance
Overvoltage category EN 61800-5-1
II >2000 m amsl
III 0 … 2000 m amsl
Insulaon of control circuits
EN 61800-5-1 Safe mains isolaon double/reinforced insulaon
Leakage current
AC
EN 61800-5-1
> 3.5 mA
Please observe regulaons and safety instrucons!
DC > 10 mA
Starng current
≤ 3 x rated mains current
Protecve measures
Earth fault resistance Earth-fault protected depending on operang status
Motor stall protecon
Short-circuit strength
Overvoltage resistance
Overtemperature of
motor
PTC or thermal contact, I²xt monitoring
EMC data
Operaon on public supply systems The machine or system manufacturer is responsible for
compliance with the requirements for the machine/
system!
> 1 kW, mains current ≤
16 A
EN 61000-3-2
no addional measures
< 1kW with mains choke
Mains current > 16 A EN 61000-3-12
With mains choke or mains
lter
When designed for rated power.
Noise emission
Category C1
EN 61800-3 See rated dataCategory C2
Category C3
Noise immunity
EN 61800-3 Requirements fullled
Technical data
EMC data
176