3-phase mains connecon 480 V
Rated data
The output currents apply to these operang condions:
•
At switching frequency 2 kHz or 4 kHz: Ambient temperature max. 45 °C (113 °F).
•
At switching frequency 8 kHz, 12 kHz or 16 kHz: Ambient temperature max. 40 °C (104 °F).
Inverter I55AP
137F 155F 175F 211F 215F 222F
Rated power P
rated
kW 0.37 0.55 0.75 1.1 1.5 2.2
Rated power P
rated
HP 0.5 0.75 1 1.5 2 3
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0 - 400/480 V
Rated mains current
without mains choke A 1.5 2.1 2.8 3.7 4.5 6.5
with mains choke A -
Apparent output power kVA 0.9 1.3 1.7 2.4 2.8 3.9
Rated output current
2 kHz A 1.1 1.6 2.1 3 3.5 4.8
4 kHz A 1.1 1.6 2.1 3 3.5 4.8
8 kHz A 1.1 1.6 2.1 3 3.5 4.8
12 kHz A 0.9 1.3 1.7 2.7 3.2 4.3
16 kHz A 0.7 1.1 1.3 2 2.3 3.2
Power loss
2 kHz W 19 24 30 38 45 62
4 kHz W 20 25 32 40 48 66
8 kHz W 24 31 40 51 61 85
12 kHz W 23 30 38 54 65 91
16 kHz W 22 28 35 49 58 81
Cyclic mains switching 3 mes per minute
Max. motor cable length
shielded
without EMC category m 50
Category C1 (2 kHz, 4 kHz,
8kHz)
m 3
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 20
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 35
Max. motor cable length
unshielded
without EMC category m 60 80
Degree of protecon
EN IP31 IP66 IP31 IP66 IP31 IP66 IP31 IP66 IP31 IP66 IP31 IP66
NEMA Type
1
Type
4X
Type
1
Type
4X
Type
1
Type
4X
Type
1
Type
4X
Type
1
Type
4X
Type
1
Type
4X
Weight m kg 1.7 1.8 1.7 1.8 1.7 1.8 2.6 2.7 2.6 2.7 2.6 2.7
Weight m lb 3.7 4 3.7 4 3.7 4 5.7 6 5.7 6 5.7 6
Technical data
3-phase mains connecon 480 V
Rated data
188