Terminal data
X1 Specicaon Unit min. typ. max.
SIA, SIB LOW signal V -3 0 +5
HIGH signal V +15 +24 +30
Switch-on me ms 3
Clear me ms 50 60
Input current SIA mA 10 14
Input current SIB mA 7 12
Input peak current mA 100
Test pulse duraon ms 1
Test pulse interval ms 10
GS Reference potenal for SIA and SIB
Connecon descripon Basic Safety - STO
Connecon X1
Connecon type Pluggable
Max. cable cross-secon mm² 1.5
Max. cable cross-secon AWG 16
Stripping length mm 9
Stripping length in 0.35
Required tool 0.4 x 2.5
Electrical installaon
Funconal safety
Basic Safety - STO
170