Terminal data
Rated power P
rated
kW 0.37 ... 5.5 7.5 ... 11
Connecon descripon Mains connecon
Connecon X100
Connecon type Non-pluggable
Max. cable cross-secon mm² 4 16
Max. cable cross-secon AWG 10 6
Stripping length mm 10 11
Stripping length in 0.4 0.43
Tightening torque Nm 0.5 1.2
Tightening torque lb-in 4.4 11
Required tool 1.2 x 8.0 0.8 x 4.0
Rated power P
rated
kW 0.37 ... 5.5 7.5 ... 11
Connecon descripon PE connecon
Connecon PE
Max. cable cross-secon mm² 6 16
Max. cable cross-secon AWG 10 6
Stripping length mm 10 11
Stripping length in 0.4 0.4
Tightening torque Nm 2 3.4
Tightening torque lb-in 18 30
Required tool T20 PZ2
Rated power P
rated
kW 0.37 ... 5.5 7.5 ... 11
Connecon descripon Motor connecon
Connecon X105
Connecon type Non-pluggable
Max. cable cross-secon mm² 4 16
Max. cable cross-secon AWG 10 6
Stripping length mm 10 11
Stripping length in 0.4 0.43
Tightening torque Nm 0.5 1.2
Tightening torque lb-in 4.4 11
Required tool 1.2 x 8.0 0.8 x 4.0
Electrical installaon
Mains connecon
3-phase mains connecon 480 V
150