Terminal data
Rated power P
rated
kW 0.75 ... 2.2
Connecon descripon Mains connecon
Connecon X100
Connecon type Non-pluggable
Max. cable cross-secon mm² 4
Max. cable cross-secon AWG 10
Stripping length mm 10
Stripping length in 0.4
Tightening torque Nm 0.5
Tightening torque lb-in 4.4
Required tool 1.2 x 8.0
Rated power P
rated
kW 0.75 ... 2.2
Connecon descripon PE connecon
Connecon PE
Max. cable cross-secon mm² 6
Max. cable cross-secon AWG 10
Stripping length mm 10
Stripping length in 0.4
Tightening torque Nm 2
Tightening torque lb-in 18
Required tool T20
Rated power P
rated
kW 0.75 ... 2.2
Connecon descripon Motor connecon
Connecon X105
Connecon type Non-pluggable
Max. cable cross-secon mm² 4
Max. cable cross-secon AWG 10
Stripping length mm 10
Stripping length in 0.4
Tightening torque Nm 0.5
Tightening torque lb-in 4.4
Required tool 1.2 x 8.0
Fusing data
Inverter Fuse Circuit breaker RCD
Characterisc
Max. rated
current
Characterisc
Max. rated
current
Type
A mA
I55AP175G..3 gG/gL, gRL 20 - - ≥30 Typ B
I55AP175G..7 gG/gL, gRL 20 - - ≥30 Typ B
I55AP215G..3 gG/gL, gRL 20 - - ≥30 Typ B
I55AP215G..7 gG/gL, gRL 20 - - ≥30 Typ B
I55AP222G..3 gG/gL, gRL 20 - - ≥30 Typ B
I55AP222G..7 gG/gL, gRL 20 - - ≥30 Typ B
Electrical installaon
Mains connecon
3-phase mains connecon 600 V
154