Inverter I55AP
230C 240C 255C 275C 311C
Rated power P
rated
kW 3 4 5.5 7.5 11
Rated power P
rated
HP 4 5 7.5 10 15
Mains voltage range 3/PE AC 195 V ... 264 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0 - 230/240 V
Rated mains current
without mains choke A 15 20.6 28.8 36.3 52.2
with mains choke A -
Apparent output power kVA 4.5 6.2 8.7 10.9 15.8
Rated output current
2 kHz A 12 16.5 23 29 42
4 kHz A 12 16.5 23 29 42
8 kHz A 12 16.5 23 29 42
12 kHz A 10.8 14.9 20.7 26.1 37.8
16 kHz A 8 11 15.3 19.3 28
Power loss
2 kHz W 79 102 137 172 242
4 kHz W 84 108 145 183 258
8 kHz W 109 140 189 238 337
12 kHz W 104 133 180 255 361
16 kHz W 104 133 180 227 321
Cyclic mains switching 3 mes per minute
Max. motor cable length
shielded
without EMC category m 50
Category C1 (2 kHz, 4 kHz,
8kHz)
m -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m -
Category C3 (2 kHz, 4 kHz, 8
kHz)
m -
Max. motor cable length
unshielded
without EMC category m 100 200
Degree of protecon
EN IP31 IP66 IP31 IP66 IP31 IP66 IP31 IP66 IP31 IP66
NEMA Type 1 Type
4X
Type 1 Type
4X
Type 1 Type
4X
Type 1 Type
4X
Type 1 Type
4X
Weight m kg 4.7 4.8 4.7 4.8 4.7 4.8 4.9 5 4.9 5
Weight m lb 10.4 10.6 10.4 10.6 10.4 10.6 10.8 11 10.8 11
Technical data
3-phase mains connecon 230/240 V
Rated data