156 L Firmware 03.00 - DMS EN 5.0 - 07/2009
MaxLimit
DINT
C00225
-199.99 % +199.99 Maximum value of the PID operating
range
Initialisation: 199.99 %
MinLimit
DINT
C00226
-199.99 % +199.99 Minimum value of the PID operating
range
•Initialisation: -199.99%
Acceleration time
DINT
C00227
0.000 s 999.999 Acceleration time for the ramp at the
PID output (should be set as steep as
possible)
Initialisation: 0.010 s
Deceleration time
DINT
C00228
0.000 s 999.999 Deceleration time for the ramp at the
PID output
Initialisation: 0.010 s
Operating mode
C00242
Value range of the output signal
•Initialisation: 0
0 Off The setpoint applied to the input
nNSet_a is output without any
changes at the output nOut_a.
1 Additive + feedforward control The setpoint is picked off at the input
nNSet_a. Simultaneously, the
setpoint is added to the output value
of the PID-component and then
output at nOut_a.
2 PID as a setpoint generator The setpoint is picked off at the input
nSet_a. The input nNSet_a is not
used. There is no additive linking at
the output.
3 PID setpoint from L_NSet_1 The setpoint is picked off at the input
nNSet_a. The input nSet_a is not
used. There is no additive linking at
the output.
Influence acceleration time
C00243
0.000 s 999.999 Acceleration time T
ir
for the
influence value
•Initialisation: 5s
Influence deceleration time
C00244
0.000 s 999.999 Deceleration time T
if
for the
influence value
•Initialisation: 5s
Identifier/data type
Index
Possible settings Info

Table of Contents