9.1.3.5 Deactivation of the process controller
bInAct = TRUE deactivates the process controller. This serves to
set the PID output = 0,
set the integral action component = 0,
set the ramp function generator = 0.
A setpoint executed in mode 1 of the input nNSet_a, however, will still be output.