POLICE EMERGENCY
This zone type activates the burglar alarm and sounder. An emergency dial out is activated after the DIAL OUT
DELAY.
DURESS EMERGENCY (SILENT DIAL OUT)
If you wish to have a button in your home that activates a SILENT dial out, (no lights flashing and no sounder) it
should be connected to a zone that is configured as a DURESS EMERGENCY. If this zone is accidentally tripped,
you will not know that the Omni LTe is making a silent dial out, and hence won't know to stop it.
To stop a silent dial out once it has started, you must go to the console and press OFF then enter your code.
SUPERVISED FIRE
Any zone can be programmed as a SUPERVISED FIRE ZONE. In UL Listed Installations, all fire detectors must be
configured as a SUPERVISED FIRE ZONE and connected as shown in this manual. When Zones 1-4 are configured
as a SUPERVISED FIRE ZONE, the corresponding Zone Jumpers (JP11-JP14) must be in the "SMK" (smoke)
position.
FIRE EMERGENCY
This zone type activates the fire alarm for a normally closed (open for alarm) and open collector (short to ground for
alarm) switches. It is not supervised as required for UL Listed Installations and shall NOT be used in such
installations.
GAS
This GAS ZONE will generate an alarm, activate the sounder (on - off - on - long off), and make a dial out. This zone
type requires an external 1000-ohm end-of-line resistor.
When Zones 1-4 are configured as a GAS ZONE, the
corresponding Zone Jumpers (JP11-JP14) must be in the "SMK" (smoke) position.
AUXILIARY EMERGENCY
This AUXILIARY EMERGENCY ZONE type will generate an alarm (console beeper - no sirens) and make an
emergency dial out when the zone is violated. An emergency dial out is activated after the DIAL OUT DELAY.
TROUBLE
This zone type can be used to monitor the status of an external device, such as the battery status of a wireless
security receiver. It can also used to record events in the event log (i.e. driveway activation, opening of a gate, etc.)
without setting off the alarm.
When the zone is tripped, the zone name will be displayed on the display as "NOT RDY". The alarm is not activated,
regardless of the security mode. The trouble is logged in the event log. The digital communicator (if used) will report
the alarm code for the zone. The voice dialer will not be activated.
FREEZE
This FREEZE ALARM ZONE type will generate an alarm (console beeper, no sirens) and make an emergency dial
out.
WATER
This WATER ALARM ZONE type will generate an alarm (console beeper, no sirens) and make an emergency dial