Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
6 - 10 Remote Access and Control Issue 13 December 2000
pas*
*You must
be logged in
as a
super-user
to use this
command.
Change
passwords
pas t,“password”,
“password”
where: “t” is “u” to
change the user
password or s” to
change the
super-user
password;
password” is the
new password
Changes either the user or super-user password. The
password is sent twice in order to avoid mistakes. The
password must have at least 6 characters but no more
than 15 characters.
sta Report status sta obj,attr
where: obj,attr is an
object-attribute
pair. Example,
ps1,sid
Reports the value of the measurement, configuration,
or control parameters in the system. Examples:
sta dc1,adc – report plant load current
sta dc1,vdc – report plant voltage
Response for this example:
* sta dc1,vdc
:DC1
VDC=-52.48 V
.
* _
(The * is the user command line prompt. The line
“:DC1” indicates that the information that
follows is for the plant object. The line starting
with “VDC” identifies the DC voltage. the “.”
line is the end-of-command identifier.)
Table 6-C: Command Descriptions
Command Syntax Description

Table of Contents