Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
6 - 8 Remote Access and Control Issue 13 December 2000
T1.317 Command Language, continued
Table 6-B: Object-Attribute Pairs – Related Commands
Obj,attr Description Sta Cha Ope Type Range of Values
ps1,des Power system description ✓ text
Lucent ES648
control unit
ps1,sid Site ID ✓✓ text up to 15 characters
ps1,swv Software version ✓ text
ES648 software
version
dc1,stt Plant state ✓ text
FLOAT, BOOST,
PBT
dc1,vdc Plant voltage ✓ number dd.dd V
dc1,adc Plant load current ✓ number ddd.d A
dc1,ubt* Plant battery temperature ✓ number dd C
br1,pbt Plant battery test state ✓✓number
0:pbt not active
1:pbt active
br1,pbte Plant battery test enable ✓ number 0:disabled 1:enabled
p1,phn Primary phone number ✓✓ text up to 25 characters
a1,phn Alternate phone number ✓✓ text up to 25 characters
gm1,fsp Rectifier set-point ✓✓ number dd.dd
gm1,ros
Rectifier on standby
control
✓✓number
0:ros not active
1:ros active
gm1,rose
Rectifier on standby
enable
✓ number 0:disabled 1:enabled
bda1,thr BD threshold ✓ number dd.dd (52.0 - 55.0)
bda1,sev BD is major or none ✓ text MAJ or NO
bs1,bse Boost enable ✓ number 0:disabled 1:enabled
sc1,typ Compensation type ✓ text NAFTA or EURO
eeq1,stt
External equipment
control state
✓✓number 0:open 1:closure
eeq1,alrn
External equipment
alarm state
✓ number
0:no alarm
1:alarm closure
eeq1,inp External equipment input ✓ number 0:open 1:closure
mp1,ins**
Modem initialization
string
✓✓ text up to 25 characters
*Although several thermal probes may be connected to a CPS system, only the highest battery
temperature is displayed. The battery temperature is displayed in degrees Celsius.
**This string of characters is sent by the ES648 control unit to the modem to initialize it into
active service. Up to 25 characters may be entered.
• cha mpl,ins = “at&fev” – change the modem initialization string to “at&fev”
• cha mpl,ins = “’’ – change the modem initialization string to the default value “at&fev&c1”