Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
3 - 18 Engineering and Ordering Issue 13 December 2000
Torque and Tool
Information for
Input Hardware
21, 22,
23, 25,
26
J6
Office Alarm
Output
847415874 Kit provides office
alarm plug, strain relief
housing, and retaining clip for
24 AWG stranded or 24-26
AWG solid wire. Order Lucent
Technologies tool R4623B or
R5250 separately.
(1) kit optional per shelf
or
848418216 Kit provides P6
plug and 150 feet of
multicolored cable
or
848418851 Kit provides P6
plug and 25 feet of
multicolored cable.
Discrete wire set
equipped with (1) Amp
552274-1 plug, (1)
Amp 552414-1 strain
relief, (1) Amp
552723-2 retaining clip
or
Ribbon cable equipped
with (1) Amp 553600-1
plug, (1) Amp
552723-2 retaining
clip.
Order Amp tool
229378-1 or 229764-2.
Table 3-E: Input Assembly Hardware
List Connector Function
Mating Connection
Lucent Technologies Commercial
Table 3-F: Torque and Tool Information for
Input Hardware
Connector Comcode Directions
TB4 847439833
Apply lugs using WT1455 or ERG2001 tool;
torque TB4 lug to 20 inch-pounds ± 10%.
J6 847415874
Apply using Lucent Technologies tools
R4623B, R5250, AMP tools 229378-1,
229764-2, or Lucent Technologies hand tool kit
900533027.