Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
7 - 6 Alarms, Controls, and Displays Issue 13 December 2000
Control Units, continued
SW1 Options,
continued
SW2 Options Switch 2 on the control units provides feature selection as outlined in
Table 7-E. Switch positions 3 through 6 are not used on any of the
control units.
Table 7-D: ES647 SW1 Options
Switch Position Feature
1
N/A
Not used
2
3 Closed
BD alarm also generates a PMJ alarm
3 Open
BD alarm does not generate a PMJ alarm
4 Closed
Enable rectifier On/Standby capability
4 Open
Disable rectifier On/Standby capability
5 Closed
Enable plant battery test
5 Open
Disable plant battery test
Table 7-E: ES648A/B/C SW2 Options
Switch Position Feature
1
Closed
Boost mode enabled after a BD event
Open
Boost mode disabled
2
Closed
NAFTA Temperature Compensation Algorithm
Open
EURO Temperature Compensation Algorithm
3
Not used
4
5
6