Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
7 - 12 Alarms, Controls, and Displays Issue 13 December 2000
Alarm Processing, continued
Table 7-H: Plant Alarm Conditions and Indications
Alarm
Condition
ES646 and
ES648A
ES646B,
ES648B, and
ES648BZ
ES648C ES647
Power
Unit
LED
BSP2/
BSP2C
LED
ES610
ES611
ES613
Office
Alarm
(Contact
Closure)
LED
Office
Alarm
(Contact
Closure)
LED
Office
Alarm
(Contact
Closure)
LED
Office
Alarm
(Contact
Closure)
LED
AC Fail (1)
PMN
ACF
PMN
ACF
PMN
ACF
PMN
ACF
PMN
ACF
PMN
ACF
PMN
ACF
PMN -- -- --
AC Fail (2)
PMJ
PMN
ACF
2ACF
PMJ
PMN
ACF
PMN
ACF
PMN
ACF
PMJ
PMN
ACF
2ACF
PMJ
PMN
ACF
PMJ
PMN
ACF
2ACF
PMJ
PMN
-- -- --
Battery on
Discharge
PMJ*
BD
PMJ*
BD
BD BD
PMJ*
BD
PMJ*
BD
PMJ*
BD
PMJ* -- -- --
Battery
Disconnect
PMJ PMJ PMJ PMJ PMJ PMJ PMJ PMJ -- -- --
Converter
or Ringer
Alarm (1)
PMN PMN PMN PMN
PMJ
PMN
Ringer/
Converter
MJF
PMJ
PMN
PMN PMN Alarm -- --
Converter
or Ringer
Alarm (2)
PMN
PMJ
PMN
PMJ
PMJ PMJ
PMJ
PMN
Ringer/
Converter
MJF
PMJ
PMN
PMJ
PMN
PMJ
PMN
Alarm -- --
Converter
Standby (1)
PMN PMN PMN PMN
PMJ
PMN
Ringer/
Converter
MJF
PMJ
PMN
PMN PMN Stby -- --
Converter
Standby (2)
PMN
PMJ
PMN
PMJ
PMJ PMJ
PMJ
PMN
Ringer/
Converter
MJF
PMJ
PMN
PMJ
PMN
PMJ
PMN
Stby -- --
Distribution
Fuse Alarm
PMJ
MJF
PMJ
MJF
PMJ
MJF
PMJ
MJF
PMJ PMJ
MJF
PMJ
MJF
PMJ -- --
PMJ or
PMN**
Excess
Battery
Temp***
PMJ PMJ PMJ PMJ PMJ PMJ PMJ PMJ -- -- --
Low
Voltage
N/A N/A
LV
(2ACF)
BD N/A N/A N/A N/A -- -- --
LVD Fail PMN PMN PMN PMN PMN PMN PMN PMN --
LVD
Fail
--