EasyManua.ls Logo

Lucent Technologies CPS4000 - Converter Plant; Table 2-I: Converter Plant Specifications

Lucent Technologies CPS4000
196 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
2 - 30 Product Description Issue 13 December 2000
Converter Plant
Table 2-I: Converter Plant Specifications
Power Units
ES680; maximum of five per shelf or 10 per plant
ES681; maximum of two per shelf or 4 per plant
Control Unit
MCU: ES646, ES646B, ES648A, ES648B, ES648C, ES648BZ
ACU: ES647
Primary Bus Required for input power via the primary bus bulk connections
Secondary Bus 24Vdc or 130Vdc
Output Voltage
ES680: 130Vdc
ES681: 24Vdc
Max. Output Current
ES680: 20 amperes per shelf
ES681: 48 amperes per shelf
Nominal Input Voltage 48/52/54Vdc
Input Voltage Range 38-60Vdc
Input Current
Typical:
ES680: 12.5 amperes per converter
ES681: 12.5 amperes per converter
Maximum:
ES680: 16 amperes per converter (Note 1)
ES681: 18 amperes per converter (Note 2)
Efficiency
ES680: 86% typical
ES681: 84% typical
Voice-band Noise
ES680: <32 dBrnc
ES681: <32 dBrnc
Load Share Accuracy
ES680: 0.4 amperes
ES681: 2.4 amperes
Operating Ambient
Temperature
-40°F to 149°F (-40°C to 65°C)
CPS plant can withstand temporary fluctuations in temperature
up to 167°F (75°C)
Note 1: Input current specified at input voltage of 54.5 volts, an output of 130 volts and
4 amperes and efficiency of 86%.
Note 2: Input current specified at input voltage of 54.5 volts, an output of 24 volts and
24 amperes and efficiency of 84.5%.