Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
6 - 6 Remote Access and Control Issue 13 December 2000
T1.317 Command Language
Introduction The command language is based on the T1.317 standard. The T1.317
standard has been adapted to the needs of a small plant control unit. This
section describes the command line log-in sequence as well as
commands, objects and attributes used to access measurements,
configuration, and control parameters in the control unit.
Objects The T1.317 standard organizes attributes into groups called objects.
Table 6-A lists the objects supported for remote access.
Table 6-A: Objects Supported for Remote Access
Identifier Description
ps1 Power system description / site name
dc1 DC plant
sc1 Slope thermal compensation type
bs1 Boost manager
bda1 BD alarm
br1 Battery reserve
p1 Primary phone number
a1 Alternate phone number
gm1 Rectifier manager
eeq1 External equipment
mp1 Modem