Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
Issue 13 December 2000 Remote Access and Control 6 - 9
Commands
Introduction This section describes each of the remote access commands supported
by this control unit.
Command
Descriptions
Table 6-C lists the syntax and description of the commands. Note that
all commands are case sensitive.
Table 6-C: Command Descriptions
Command Syntax Description
ala Report active
alarms
ala Reports all the active alarm conditions in the plant.
One alarm message is listed per line in the report.
Table 6-D lists the available alarm messages and a
brief description of each. Refer to Section 7, Alarms,
Controls, and Displays, for specific details
concerning the criteria for issuing alarms.
bye Log-off bye Terminates the remote access session. If the user is
connected via a modem, the control unit will
disconnect the user.
cha*
*You must
be logged in
as a
super-user
to use this
command.
Change value cha,obj,attr=value
where: obj,attr is an
object-attribute
pair.
For example:
ps1,sid
Changes system configuration parameters.
Examples:
cha ps1,sid=“My Plant” – change the site id to
My Plant
cha p1,phn=“123456789” – change the primary
phone number to 123456789
login Log-in login “password
where: password is
either the user or
super-user
password
Log-in as a user or super-user. For example, if you are
currently logged in to the control unit as a user but
would like to change the site id, you must first use
this command to log-in as a super-user.
ope*
*You must
be logged in
as a
super-user
to use this
command.
Operate a
control
ope obj,attr=value
where: obj.attr is an
object-attribute
pair.
For example,
dc1,pbt
Operates a system control parameter. Examples are
listed below to illustrate how this command operates:
ope dc1,pbt=1 – start a plant battery test
ope eeq1,stt=1 – close the external equipment
control relay