Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
7 - 14 Alarms, Controls, and Displays Issue 13 December 2000
Office Alarm Contacts
Introduction These are 60-volt, 0.5-ampere, Form-C or transfer type contacts that
allow an installer to connect the control unit to an office alarm system.
Each set of isolated contacts consists of a combination of normally open
(NO) and normally closed (NC) contacts with one side of each common
(C). When the control unit has power and no alarm condition exists, all
alarm relays are energized. When an alarm condition exists, the relay
de-energizes and a closure exists between the NC and C poles and an
open exists between the NO and C poles. If the control unit is powered
down, the alarm relays are de-energized and all NC and NO closures are
sent to the office alarm system.
ES646, ES647,
ES648A Control
Units
A set of Form-C contacts is brought out on J6 for each of the following
plant alarms for the ES646, ES647, and ES648A:
• Power Major (PMJ)
• Power Minor (PMN)
• Battery on Discharge (BD)
• AC Fail (ACF)
• Two-AC Fail (2ACF)
• Major Fuse Alarm (MJF)
ES646B, ES648B,
and ES648BZ
Control Units
The set of Form-C office alarm contacts for the ES646B, ES648B, and
ES648BZ is as follows:
• Power Major (PMJ)
• Power Minor (PMN)
• Battery on Discharge (BD)
• AC Fail (ACF)
• Low Voltage (LV)
• Major Fuse Alarm (MJF)
ES648C Control
Unit
The set of Form-C office alarm contacts for the ES648C is as follows:
• Power Major (PMJ)
• Power Minor (PMN)
• Battery on Discharge (BD)
• AC Fail (ACF)
• 2AC Fail (2ACF)
• Ringer/Converter Fail