Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
Issue 13 December 2000 Alarms, Controls, and Displays 7 - 19
External Equipment
External
Equipment Alarm
The external equipment alarm applies to the ES648 control units only.
Refer to Table 7-I for external equipment alarm connections to the
ES648 control unit.
There are no visual or audible alarms on the CPS shelf that are
associated with the External Equipment Alarm. A fan that generates an
isolated contact closure if it has failed or a door interlock that generates
an isolated contact closure if the door is open may be connected to J6-33
and J6-32. The status of this alarm can be determined by using the
remote access feature with T1.317 commands or with EasyView
software.