EasyManua.ls Logo

Lucent Technologies CPS4000 - Page 35

Lucent Technologies CPS4000
196 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
Issue 13 December 2000 Product Description 2 - 13
Power Modules, continued
Features,
continued
Output current limit: Power modules provide a constant output
voltage up to their rated output current, at which point they begin to
provide constant current outputs. The maximum output current is
inherently limited to less than 110% of the rated output without user
adjustment.
Internal selective high-voltage shutdown: If the plant voltage
goes too high, only the defective power module will shut down.
Backup high-voltage shutdown: If the internal high-voltage
shutdown fails, a backup is provided that is faster and is set to 60
volts.
Restart circuit: If a rectifier or converter has shut down due to
high plant output voltage, it will attempt to restart a maximum of
two times automatically. After two unsuccessful attempts, the
power module shuts down and locks down. This assumes that a
battery is present to maintain the circuitry on the MCU or ACU.
Ringer redundancy: If a ringer fails, that ringer will be
automatically removed from service and a hot on-line redundant
ringer will be switched into service.
Power module alarm: The power module alarm provides both a
local visual indication of low output voltage and a signal to the
plant MCU or ACU. In addition, alarms are generated by a high
module temperature and/or an operated internal fuse.
Thermal alarm: The -48V CPS rectifiers and converters are fan
cooled to increase their reliability. Excess internal temperature
caused by fan failure or other conditions initiates a thermal alarm.
Power factor: State-of-the-art circuits in the rectifiers increase the
power factor to near unity.
Total harmonic distortion: By controlling the power factor, the
total harmonic distortion is reduced to less than 5% at full load, less
than 15% at half load.
Voltage range selection: CPS power modules automatically accept
a wide range of ac input voltages.